What it is

What is CO₂ as an air quality parameter?

Carbon dioxide (CO₂) is a colorless, odorless gas that people exhale continuously. Outdoor air sits at roughly 420 ppm and rising. Indoors, CO₂ accumulates in proportion to how many people occupy a space and how little fresh air is supplied to dilute it. That makes indoor CO₂ the most practical proxy for ventilation adequacy. It does not measure pollutants directly, but it shows whether a room is getting enough outdoor air to carry pollutants, pathogens, and odors away.

Because the signal is cheap to measure and easy to interpret, CO₂ has become the headline number of the healthy-building and classroom-ventilation movements.

Health and operational effects

At the concentrations found in ordinary buildings CO₂ is not directly toxic, but rising levels track stuffiness, drowsiness, and measurable declines in concentration and decision-making; studies have shown cognitive scores falling as indoor CO₂ climbs through the 1,000–1,500 ppm range. High CO₂ also signals that whatever else occupants emit, from bioeffluents to airborne viruses, is being under-diluted, which is why ventilation guidance surged in importance after 2020.

Operationally, CO₂ is the control signal for demand-controlled ventilation: instead of running air handlers at a fixed rate, a building modulates fresh-air intake to actual occupancy, saving heating and cooling energy while protecting air quality.

Limits

Carbon Dioxide (CO₂) Limit Values

The published values, by averaging period; each links to the standard that sets it.

8-hour TWA (PEL)

A03 Ventilation Design, monitoring option

A06 Enhanced Ventilation Design (points)

95th percentile, continuous

High performance

Sustained, above ambient

  • WELL v2 900 ppm: or no more than 500 ppm above outdoor; one of four ways to meet the precondition
  • WELL v2 750 ppm: or no more than 350 ppm above outdoor
  • UBA CO₂ 1000 ppm: < 1000 ppm: hygienically acceptable
  • UBA CO₂ 2000 ppm: > 2000 ppm: hygienically unacceptable
  • LEED v5 1000 ppm: 3 points at or below
  • LEED v5 800 ppm: 4 points at or below
  • RESET Air 1000 ppm: below
  • RESET Air 600 ppm: below
  • ISO 23875 400 ppm: cab CO₂ no more than 400 ppm above ambient (clause 4.1)

CO₂ is reported in parts per million (ppm). The widely used rule of thumb, reflected in the German UBA guideline, treats sustained readings below 1,000 ppm as hygienically adequate and above 2,000 ppm as unacceptable. The WELL Building Standard uses CO₂ as a ventilation indicator: sensor data showing 900 ppm or less (or 500 ppm above outdoor) meets its ventilation precondition, and 750 ppm (or 350 ppm above outdoor) earns enhanced-ventilation points. Interpret CO₂ as a trend against occupancy, not as an instantaneous pass/fail. A brief peak in a packed meeting room matters less than a level that never recovers between sessions.

Methods and guidance

How it is measured

How Carbon Dioxide (CO₂) Is Measured

The dominant technology is non-dispersive infrared (NDIR). CO₂ absorbs infrared light at a characteristic wavelength, so the sensor passes an IR beam through a sample chamber and measures how much is absorbed. NDIR is selective, stable, and long-lived. The main accuracy pitfall is calibration drift. Many sensors use an automatic baseline correction that assumes the space periodically returns to outdoor levels, which can misread in spaces occupied around the clock. It is worth checking for hospitals, nursing homes, and 24-hour operations.

Photoacoustic and chemical sensors also exist, but NDIR is the workhorse for building monitoring.

Built into Aethair IAQ1

Measured by the monitor's own sensors, calibrated before it ships: nothing to add.

Aethair PRO cartridges2

A pre-calibrated cartridge in one of Aethair PRO's sockets: Aethair CO₂ (dual NDIR) and Aethair CO₂ (self-calibrating NDIR).

An instrument on Thiamis3

A third-party instrument connected to a Thiamis gateway, reporting into the same Environet account.

Placing CO₂ sensors

Mount CO₂ sensors at breathing height in the occupied zone, away from doors, operable windows, and supply diffusers where fresh air would give an artificially low reading, and away from anyone's direct exhalation. Wall-mounted units at 1.1–1.5 m are typical for offices and classrooms. One sensor represents one ventilation zone; open-plan spaces with uneven occupancy may need several.

Every device and option that measures Carbon Dioxide (CO₂) 5

Device / optionTypeBase platformMeasures
Aethair IAQ built-in sensors
Built-in sensors
Aethair IAQ
Aethair CO₂ (dual NDIR) 0d02 0d04
Gas sensor cartridge
Aethair PRO
Particles Plus · Particles Plus 5301, Particles Plus 5301-AQM1, Particles Plus 5301-AQM2…
Particulate & Dust Monitors
Thiamis
RAE · MultiRAE Lite, MultiRAE, MultiRAE Pro…
Gas Detectors
Thiamis
Trolex · Sentro X (TX6310)
Gas Detectors
Thiamis

Configure Carbon Dioxide (CO₂) Monitoring

Where it is monitored

Solutions That Monitor Carbon Dioxide (CO₂)

Each one links to the solution page showing what that industry measures it for.

Article Library

Reading on Carbon Dioxide (CO₂)

All articles

Related

Questions

Carbon Dioxide (CO₂) FAQ

What CO₂ level indicates poor ventilation?

Sustained indoor CO₂ above about 1,000 ppm suggests ventilation is not keeping pace with occupancy; above 1,500–2,000 ppm indicates clearly inadequate fresh air. Because outdoor air is around 420 ppm, the excess over that baseline is what reflects human occupancy and dilution.

Does CO₂ measure air pollution directly?

No. CO₂ itself is not a pollutant at building concentrations; it is a proxy. It indicates whether a space is well ventilated, which in turn governs the buildup of pollutants, odors, and exhaled aerosols. For pollutants themselves, pair CO₂ with PM2.5 and VOC monitoring.

What is the best sensor technology for CO₂?

Non-dispersive infrared (NDIR) is the standard for building and IAQ monitoring: selective, stable, and durable. Check whether a given sensor relies on automatic baseline calibration, which can be inaccurate in continuously occupied spaces.

How can I monitor CO₂ in my building?

Aethair IAQ measures CO₂ with a built-in NDIR sensor (Aethair PRO takes a CO₂ cartridge). That makes it a single-device fit for most indoor air quality and ventilation programs. Use the configurator to add PM2.5, VOC, temperature, and humidity for a complete healthy-building configuration.